Precision cooling
Rack-mounted or in-row precision AC with inverter compressor and EC fans, low-load anti-condensation and N+X group control.
Select a model to highlight it in the specification table.
RDC-05 is pictured with a four-cabinet configuration for illustration.
The first cabinet holds UPS, distribution and monitoring alongside IT space; the others are 42U IT cabinets. Scroll sideways on small screens.
| Parameter | RDC-011 cabinet | RDC-022 cabinets | RDC-033 cabinets | RDC-055 cabinets | RDC-077 cabinets |
|---|---|---|---|---|---|
| Power supply & distribution | |||||
| UPS capacity | 3 kVA | 6 kVA | 10 kVA | 20 kVA | On request |
| Power factor | 0.8 | 0.8 | 0.8 | 0.9 | On request |
| Total input | 220 V / 40 A | 220 V / 63 A | 220 V / 125 A | 380 V / 125 A | On request |
| UPS height | 4U | 4U | 4U | 6U | On request |
| Protection | Class C lightning protection · ATS module optional | ||||
| Cabinet | |||||
| Cabinets | 1 | 2 | 3 | 5 | 7 |
| Usable IT space | 28U | 33U + 42U | 29U + 2×42U | 30U + 4×42U | On request |
| PDU per rack | 8-way 10 A | 12-way 10 A | 12-way 10 A | 12-way 10 A + 4-way 16 A | On request |
| Aisle | Fully enclosed hot and cold aisle | ||||
| Emergency ventilation | Fan type, up to 5 kW, automatic start and stop | ||||
| Cooling | |||||
| Type | Rack mount | In-row | In-row | In-row | In-row |
| Cooling capacity | 3.5 kW | 7.5 kW | 12.5 kW | 2 × 12.5 kW | On request |
| System | Compressor + EC fans · sensible heat ratio 1 | ||||
| Battery | |||||
| Standard batteries | 8 | 16 | 16 | 20 | On request |
| 15 min backup | 2U pack | 3U pack | — | 6U pack | On request |
| 40 min backup | — | — | — | Ext. 20 × 100 Ah / 12 V | On request |
| Longer runtime | Higher-capacity batteries or up to 4 additional packs | ||||
| Physical & environment | |||||
| W × D × H (mm) | 600 × 1200 × 2000 | 1500 × 1200 × 2000 | 2100 × 1200 × 2000 | 3600 × 1200 × 2000 | On request |
| Operating range | 0–45 °C · 0–95% RH non-condensing · <1000 m without derating | ||||
| Fire | 1U rack-mounted heptafluoropropane system (optional) | ||||