Which servers fit? Any server, 1U to 21U.
NexisImmersion tanks take standard 19″ rack servers, not proprietary hardware. Any server from 1U up to 13U fits the 13U tank; any server up to 21U fits the 21U tank. Mix heights freely.
Two things decide the fit
1 · Space
The rack units of all servers added together must not exceed the tank: 13U or 21U. U positions are customisable, so any mix of heights works.
2 · Heat
The maximum power draw of all servers added together must not exceed the tank's rated heat exchange, 4 to 40 kW. Size for peak load, not average.
Power budget by model
| Model | Tank | Rated heat | Server height | kW per U (full) | Example fill |
|---|---|---|---|---|---|
| NXL-04 | 13U | 4 kW | 1U – 13U | 0.31 | 8 × 1U edge servers at 450 W = 3.6 kW · 8U |
| NXL-06 | 13U | 6 kW | 1U – 13U | 0.46 | 6 × 2U servers at 900 W = 5.4 kW · 12U |
| NXL-10 | 13U or 21U | 10 kW | 1U – 13U/21U | 0.77 (13U) · 0.48 (21U) | 3 × 4U GPU servers at 3 kW = 9 kW · 12U (13U tank), or 20 × 1U at 450 W = 9 kW · 20U (21U tank) |
| NXL-20 | 21U | 20 kW | 1U – 21U | 0.95 | 4 × 4U GPU servers at 4.5 kW = 18 kW · 16U |
| NXL-40 | 21U | 40 kW | 1U – 21U | 1.90 | 5 × 4U GPU servers at 7.5 kW = 37.5 kW · 20U |
Examples are planning illustrations, not validated configurations.
Servers that gain most
GPU & AI servers
2U–8U accelerator nodes for training and inference. Highest heat per U, quietest result.
Dense compute
1U and 2U dual-socket nodes for virtualisation, HPC and edge.
All-flash storage
NVMe and SSD storage nodes. Solid-state only, no spinning disks.
Telecom & BBU
5G baseband units and edge appliances on universal mounting.
Preparing a server for immersion
Semita prepares servers at commissioning, or your team can follow this list.
1 · Fans out
Remove or disable server fans; set BMC/firmware so missing fans do not raise alarms or throttle.
2 · Solid-state storage
SSD and NVMe only. Unsealed spinning drives cannot run submerged.
3 · Thermal interface
Replace standard paste with an immersion-rated compound, or use indium or graphite pads.
4 · Labels & foam
Remove paper labels, stickers and foam inserts; they lift and float.
5 · Silicone oil check
Confirm silicone-based pads, gaskets and cable jackets are rated for silicone oil.
6 · Optics above the oil
Keep transceivers and fiber connectors above the surface; use DAC inside the tank.
7 · Power supplies
Confirm each PSU is suitable for immersion, or use the tank's power distribution.
8 · Warranty
Confirm immersion warranty terms with the server vendor before deployment.
Pre-deployment checklist
- Company and site
- Server make and model
- Height (U) × quantity
- Maximum power per server (W)
- Storage type
- In-tank network
- Target NXL model
- Site power available