NexisImmersion · Server compatibility

Which servers fit? Any server, 1U to 21U.

NexisImmersion tanks take standard 19″ rack servers, not proprietary hardware. Any server from 1U up to 13U fits the 13U tank; any server up to 21U fits the 21U tank. Mix heights freely.

Two things decide the fit

1 · Space

The rack units of all servers added together must not exceed the tank: 13U or 21U. U positions are customisable, so any mix of heights works.

2 · Heat

The maximum power draw of all servers added together must not exceed the tank's rated heat exchange, 4 to 40 kW. Size for peak load, not average.

Power budget by model

ModelTankRated heatServer heightkW per U (full)Example fill
NXL-0413U4 kW1U – 13U0.318 × 1U edge servers at 450 W = 3.6 kW · 8U
NXL-0613U6 kW1U – 13U0.466 × 2U servers at 900 W = 5.4 kW · 12U
NXL-1013U or 21U10 kW1U – 13U/21U0.77 (13U) · 0.48 (21U)3 × 4U GPU servers at 3 kW = 9 kW · 12U (13U tank), or 20 × 1U at 450 W = 9 kW · 20U (21U tank)
NXL-2021U20 kW1U – 21U0.954 × 4U GPU servers at 4.5 kW = 18 kW · 16U
NXL-4021U40 kW1U – 21U1.905 × 4U GPU servers at 7.5 kW = 37.5 kW · 20U

Examples are planning illustrations, not validated configurations.

Servers that gain most

GPU & AI servers

2U–8U accelerator nodes for training and inference. Highest heat per U, quietest result.

Dense compute

1U and 2U dual-socket nodes for virtualisation, HPC and edge.

All-flash storage

NVMe and SSD storage nodes. Solid-state only, no spinning disks.

Telecom & BBU

5G baseband units and edge appliances on universal mounting.

Preparing a server for immersion

Semita prepares servers at commissioning, or your team can follow this list.

1 · Fans out

Remove or disable server fans; set BMC/firmware so missing fans do not raise alarms or throttle.

2 · Solid-state storage

SSD and NVMe only. Unsealed spinning drives cannot run submerged.

3 · Thermal interface

Replace standard paste with an immersion-rated compound, or use indium or graphite pads.

4 · Labels & foam

Remove paper labels, stickers and foam inserts; they lift and float.

5 · Silicone oil check

Confirm silicone-based pads, gaskets and cable jackets are rated for silicone oil.

6 · Optics above the oil

Keep transceivers and fiber connectors above the surface; use DAC inside the tank.

7 · Power supplies

Confirm each PSU is suitable for immersion, or use the tank's power distribution.

8 · Warranty

Confirm immersion warranty terms with the server vendor before deployment.

Pre-deployment checklist

  • Company and site
  • Server make and model
  • Height (U) × quantity
  • Maximum power per server (W)
  • Storage type
  • In-tank network
  • Target NXL model
  • Site power available