Immersion cooling, in a single unit.

Servers sit directly in dielectric oil inside one stainless-steel tank cabinet. Tank, circulation, heat exchange and controls share one enclosure: up to 40 kW per unit, no separate CDU, no plant room.

Semita Nexis NexisImmersion Single-Unit Liquid Immersion Cooling Tank (NXL Series)
Heat exchange per unit
4–40 kW
Tank sizes
13U · 21U
Cooling PUE
≈ 1.0
Oil inlet / outlet
40 / 50 °C
How it works

From chip to coolant, inside one tank

  1. Hardware is submerged

    Fanless servers or BBUs mount vertically, fully covered by dielectric oil.

  2. Oil absorbs the heat

    Oil enters at about 40 °C and flows over every component.

  3. Heat leaves the tank

    Warm oil at about 50 °C exchanges its heat through the unit's pipe interface.

  4. Cooled oil returns

    It re-enters at the base of the tank and the loop repeats.

Why immersion, why one unit

High power density

Direct contact between hardware and oil removes heat far better than air, so more compute fits in less floor space.

Near-ideal efficiency

No server fans and minimal cooling overhead bring cooling overhead close to zero and lower total cost of ownership.

Ultra-quiet

With fans removed, the unit runs nearly silently: fine for offices, labs and shared spaces.

Stainless & sealed

Every wetted part is stainless steel. Sealed oil keeps dust and humidity away from hardware.

Flexible layout

Customisable U positions, side or bottom pipe entry, quick deployment unaffected by climate.

Easy service

Top access door; service with fluid circulating or stopped, close to air-cooled maintenance.

Technical data

NXL specifications

ParameterNXL-04NXL-06NXL-10 13UNXL-10 21UNXL-20NXL-40
Heat exchange4 kW6 kW10 kW10 kW20 kW40 kW
Available U slots13U13U13U21U21U21U
Pipe interfaceDN25DN25DN32DN32DN40DN50
Cooling mediumSilicone (recommended), mineral, synthetic oil
Oil inlet / outlet40 / 50 °C40 / 50 °C40 / 50 °C40 / 50 °C40 / 50 °C40 / 50 °C
W × D × H (mm)1200 × 800 × 12501200 × 800 × 12501200 × 800 × 12501500 × 800 × 12501500 × 800 × 12501500 × 800 × 1250
Unit weight (empty)245 kg245 kg245 kg350 kg350 kg350 kg
Power supply1~220 V, 50 Hz1~220 V, 50 Hz1~220 V, 50 Hz3~380 V, 50 Hz3~380 V, 50 Hz3~380 V, 50 Hz

Every unit: customisable U positions · top access door with viewing window · side or bottom pipe connections · all wetted parts stainless steel · universal server and BBU mounting. Air-liquid variant available for small rooms without outdoor space: it releases heat to room air and needs no external cold source. Specifications subject to change without notice. Final values are confirmed in each quotation.

Where it fits

AI inference

GPU nodes for small and medium clusters.

Telecom base stations

BBUs and edge compute at cell sites.

Edge micro DC

Dense compute where space is scarce.

Labs & R&D

Liquid cooling validation platforms.

Server compatibility

Any standard server, 1U to 21U

Two things decide the fit: total rack units must not exceed the tank, and total peak power must not exceed its rated heat exchange.

Server compatibility guide cover

NexisImmersion FAQs

Where does the heat go?

Through the pipe interface to a site water loop, usually a dry cooler or existing chilled water, which Semita sizes and can supply. The air-liquid variant releases heat to room air and needs no external cold source.

Which fluid do you use?

Silicone oil is recommended. Mineral, synthetic and fluorinated fluids are supported, so the fluid can match a server vendor's requirements.

Will it affect my server warranty?

Standard servers may lose vendor warranty once immersed. For vendor backing, choose an immersion-ready server family and the fluid it was validated with. Ask us for the list.

How do fiber links work?

Optical transceivers and connectors stay above the oil. Inside the tank, use DAC copper cables.

Can my floor take it?

Filled, a tank weighs far more than its empty 245 or 350 kg. Floor loading is checked at site check.

How long from order to go-live?

Typically 8–12 weeks including fluid supply. Installation, filling and commissioning on site take a few days.

Does the oil need replacing?

The fluid is designed for long service life in a sealed tank. It is sampled and topped up during maintenance visits rather than routinely replaced.

Engineering & Procurement Guide

NexisImmersion Liquid Cooling: Deployment Scope & FAQs

How Semita Nexis engineers, tests and supports NexisImmersion Liquid Cooling across Indian enterprise, telecom and edge data center sites.

Factory Integration & 100% Pre-Dispatch Testing

Every system and connectivity assembly supplied by Semita Nexis is built under ISO 9001:2015, ISO 14001:2015 and ISO 45001:2018 quality management across our five Indian manufacturing units in Bengaluru, Mysore, Bhiwadi and Surat. Optical assemblies undergo 100% insertion-loss and return-loss verification, RF assemblies are PIM and VSWR swept, and micro data center racks undergo full thermal and UPS load testing prior to dispatch.

Pan-India Site Check, Installation & SLA Support

Our own field engineering teams conduct pre-deployment site checks covering power, earthing, floor loading, thermal heat rejection and cable pathways. We deliver complete bills of quantities (BOQs), CAD layout drawings, on-site commissioning and annual maintenance contracts (AMC) with 24×7 remote telemetry monitoring and guaranteed response SLAs.

How quickly can Semita Nexis deliver and commission NexisImmersion Liquid Cooling in India?

Standard connectivity, optical transceivers, fiber cables and rack accessories ship from our Indian plants within 1 to 3 weeks. Pre-integrated NexisRack micro data centers typically ship in 6 to 10 weeks and NexisImmersion liquid cooling systems in 8 to 12 weeks, with on-site installation and commissioning completed in a few days.

Can Semita Nexis customize configurations and provide project BOQs?

Yes. Our application engineers size and customize fiber core counts, trunk breakout lengths, transceiver vendor coding, rack U-heights, UPS battery runtimes and cooling capacities to match your exact site and workload. Contact our engineering team at sales@semita.in or +91-92122-94293 for a tailored BOQ within one business day.

What certifications and test reports accompany each shipment?

All deliveries include factory serialized test reports (OTDR traces, IL/RL certificates, PIM sweep charts or integrated rack FAT protocols) along with ISO 9001/14001/45001, RoHS, CE and applicable DoT/TEC conformity documentation.

Ready to try immersion?

Start with a single-unit pilot sized to your servers and load.