Brochures & Technical Guides Semita Technologies & Semita Nexis Corporate Overview & Product Specifications 2026 Datasheets
Semita Technologies — Semita & Nexis Contact us
NexisRack · NXM-3

NexisRack NXM-3

A three-rack row with 12.5 kW in-row cooling and a 10 kVA UPS. Enough space for compute, storage and network for a campus, plant or hospital.

Racks
3
UPS
10 kVA
Cooling
12.5 kW
IT space
29U + 2 × 42U

Semita Nexis · Data center infrastructure by Semita Technologies

NXM-3 specifications

Power supply & distribution
UPS capacity10 kVA
Power factor0.8
Total input220 V / 125 A · Single-phase
ProtectionClass C lightning protection; ATS module optional
PDU per rack12-way 10 A
Rack
Racks3
Usable IT space29U + 2 × 42U
AisleFully enclosed hot and cold aisle
Protection ratingIP50 standard; IP55 optional
Noise≤ 49 dB at full load
Emergency ventilationFan type, up to 5 kW, automatic start/stop
Cooling
TypeIn-row
Capacity12.5 kW
SystemInverter compressor + EC fans, SHR 1, ±0.5 °C
Battery
Standard batteries16
15 min backup—
40 min backup—
Longer runtimeHigher-capacity batteries or up to 4 extra packs
Physical & environment
W × D × H (mm)2100 × 1200 × 2000
Operating range0–45 °C, 0–95% RH non-condensing, <1000 m without derating
FireOptional 1U heptafluoropropane system
Monitoring
Display10.1″ 0U touchscreen
SensingUPS, distribution, cooling, temperature, humidity, smoke, leakage, doors
RemoteWeb, app, SMS alarms; multi-site platform

Specifications subject to change without notice. Final values are confirmed in each quotation.

Where NXM-3 fits

  • Manufacturing plants
  • Hospitals and campuses
  • Government edge rooms
  • Edge AI Pod with NXL-20/40

Not sure? Use the NexisRack sizer or send us your load.

Semita Nexis NexisRack NXM-3 Three-Rack Edge Micro Data Center Row
Engineering & Procurement Guide

NexisRack NXM-3: Deployment Scope & FAQs

How Semita Nexis engineers, tests and supports NexisRack NXM-3 across Indian enterprise, telecom and edge data center sites.

Factory Integration & 100% Pre-Dispatch Testing

Every system and connectivity assembly supplied by Semita Nexis is built under ISO 9001:2015, ISO 14001:2015 and ISO 45001:2018 quality management across our five Indian manufacturing units in Bengaluru, Mysore, Bhiwadi and Surat. Optical assemblies undergo 100% insertion-loss and return-loss verification, RF assemblies are PIM and VSWR swept, and micro data center racks undergo full thermal and UPS load testing prior to dispatch.

Pan-India Site Check, Installation & SLA Support

Our own field engineering teams conduct pre-deployment site checks covering power, earthing, floor loading, thermal heat rejection and cable pathways. We deliver complete bills of quantities (BOQs), CAD layout drawings, on-site commissioning and annual maintenance contracts (AMC) with 24×7 remote telemetry monitoring and guaranteed response SLAs.

How quickly can Semita Nexis deliver and commission NexisRack NXM-3 in India?

Standard connectivity, optical transceivers, fiber cables and rack accessories ship from our Indian plants within 1 to 3 weeks. Pre-integrated NexisRack micro data centers typically ship in 6 to 10 weeks and NexisImmersion liquid cooling systems in 8 to 12 weeks, with on-site installation and commissioning completed in a few days.

Can Semita Nexis customize configurations and provide project BOQs?

Yes. Our application engineers size and customize fiber core counts, trunk breakout lengths, transceiver vendor coding, rack U-heights, UPS battery runtimes and cooling capacities to match your exact site and workload. Contact our engineering team at sales@semita.in or +91-92122-94293 for a tailored BOQ within one business day.

What certifications and test reports accompany each shipment?

All deliveries include factory serialized test reports (OTDR traces, IL/RL certificates, PIM sweep charts or integrated rack FAT protocols) along with ISO 9001/14001/45001, RoHS, CE and applicable DoT/TEC conformity documentation.