NexisODC NXO-10 Outdoor Cabinet

10U ground-mount outdoor cabinet with 1600 W heat exchanger cooling for baseband and transport units.

Rack space
10U
HEX
1600 W
Rating
IP65
Output
8 kW -48 V DC

Semita Nexis · Data center infrastructure by Semita Technologies

Specifications

Capacity
Rack space10U, 19″ (IEC 60297-3-100)
EquipmentBaseband and transport units; vendor agnostic
Environment
Ingress protectionIP65
Classes (ETSI EN 300 019-1-1)1.2 storage · 2.3 transport · 4.1 operation
Relative humidity15–100%
Climate · heat exchanger
Temperature range-33 °C to +55 °C
Cooling capacity1600 W
Mechanical
Dimensions (H × W × D)1200 × 650 × 700 mm incl. 150 mm base frame
Weight< 95 kg, excluding active equipment
MountingGround
MaterialGalvanized steel
ColourPowder paint, RAL 7035
Door / lockFront access · padlock
Power system
Input voltage-48 V DC
Operating input range-40.0 to -58.5 V DC
Max input current200 A
Output voltage range-39.5 to -58.5 V DC
Output loadMax 8 kW: priority up to 2.5 kW, main up to 7 kW
Circuit breakers10 priority load · 13 main load
Cable I/O
Entry pointBottom; plinth access from rear and side
DC in (battery feed)4 × Ø19 mm
DC out (shielded)18 × Ø10–18 mm
Signal outlet / inlet10 × Ø10 mm / 8 × Ø6 mm
Optical22 × Ø6 mm
Punched holes3 × Ø26 mm
Remote management
External alarmsDoor · fan · HEX · DC SPD

Specifications subject to change without notice. Final values are confirmed in each quotation.

Engineering & Procurement Guide

NexisODC NXO-10: Deployment Scope & FAQs

How Semita Nexis engineers, tests and supports NexisODC NXO-10 across Indian enterprise, telecom and edge data center sites.

Factory Integration & 100% Pre-Dispatch Testing

Every system and connectivity assembly supplied by Semita Nexis is built under ISO 9001:2015, ISO 14001:2015 and ISO 45001:2018 quality management across our five Indian manufacturing units in Bengaluru, Mysore, Bhiwadi and Surat. Optical assemblies undergo 100% insertion-loss and return-loss verification, RF assemblies are PIM and VSWR swept, and micro data center racks undergo full thermal and UPS load testing prior to dispatch.

Pan-India Site Check, Installation & SLA Support

Our own field engineering teams conduct pre-deployment site checks covering power, earthing, floor loading, thermal heat rejection and cable pathways. We deliver complete bills of quantities (BOQs), CAD layout drawings, on-site commissioning and annual maintenance contracts (AMC) with 24×7 remote telemetry monitoring and guaranteed response SLAs.

How quickly can Semita Nexis deliver and commission NexisODC NXO-10 in India?

Standard connectivity, optical transceivers, fiber cables and rack accessories ship from our Indian plants within 1 to 3 weeks. Pre-integrated NexisRack micro data centers typically ship in 6 to 10 weeks and NexisImmersion liquid cooling systems in 8 to 12 weeks, with on-site installation and commissioning completed in a few days.

Can Semita Nexis customize configurations and provide project BOQs?

Yes. Our application engineers size and customize fiber core counts, trunk breakout lengths, transceiver vendor coding, rack U-heights, UPS battery runtimes and cooling capacities to match your exact site and workload. Contact our engineering team at sales@semita.in or +91-92122-94293 for a tailored BOQ within one business day.

What certifications and test reports accompany each shipment?

All deliveries include factory serialized test reports (OTDR traces, IL/RL certificates, PIM sweep charts or integrated rack FAT protocols) along with ISO 9001/14001/45001, RoHS, CE and applicable DoT/TEC conformity documentation.