GPU servers have changed the arithmetic of cooling. A single 4U accelerator server can draw 4–7 kW; four of them in a rack is already beyond what most air-cooled rooms were designed for.
How far can air go?
With good containment, blanking panels and in-row cooling, air handles roughly 10–20 kW per rack comfortably. Beyond that, fans, airflow and inlet temperatures become difficult to manage, and server fans themselves consume a noticeable share of IT power.
What immersion changes
In single-phase immersion, servers sit directly in a dielectric oil. Oil carries heat far better than air, so every component is cooled evenly and fans are no longer needed. In a NexisImmersion tank, oil enters at about 40 °C, leaves at about 50 °C, and gives up its heat through the unit's own exchanger to a dry cooler or chilled-water loop. Cooling overhead becomes very small.
A practical crossover
| Per-rack load | Usual best fit |
|---|---|
| Up to ~10 kW | Air: NXR/NXH racks or NexisRack |
| 10–20 kW | Air with containment and in-row cooling; immersion if noise or space matter |
| 20–40 kW | Immersion: NexisImmersion NXL-20 or NXL-40 |
What to check before you move to immersion
- Server preparation: fans out, SSD/NVMe only, immersion-rated thermal interface.
- Warranty: confirm terms with your server vendor or choose an immersion-ready server family.
- Heat rejection: a dry cooler position or an existing chilled-water loop.
- Floor loading: a filled tank weighs far more than its empty weight.
See the server compatibility guide or size a tank with the immersion sizer.