Every optical link needs the transmitter at one end to reach the receiver at the other. With duplex LC that is a simple A-to-B crossover. With 8, 12 or 16 fibers in one MPO connector, the cabling has to do the crossover in a planned way. That plan is the polarity method.
Method A
Straight-through trunk (fiber 1 to fiber 1) with key-up to key-down adapters. The crossover happens in one of the patch cords, so the two ends use different patch cords.
Method B
Flipped trunk (fiber 1 to fiber 12) with key-up to key-up adapters. Both ends use the same patch cord type. Method B is the common choice for parallel optics because it keeps lanes aligned without special cords.
Method C
Pair-flipped trunk, where each adjacent fiber pair is swapped inside the trunk. It works well for duplex applications but is less suited to parallel optics.
Practical advice
- Choose one method for the whole site and document it.
- Label trunks and cassettes with the method and the TIA-598 colour order.
- Test polarity during certification, not after the switches arrive.